CISA warns of unpatched critical flaw in Danfoss supermarket refrigeration controllers
The flaw needs no login and could give an attacker code execution on controllers that run supermarket cooling, and no patch exists yet.
By Mr Elite Published Updated 10 min read
- Severity
- Critical
- Status
- Reported by outlets
- Sources
- 3
- Last checked
Latest updates
- The Hacker News and Security Affairs reported that CISA added three older Danfoss AK-SM 800A flaws (CVE-2023-25914, CVE-2023-25915 and CVE-2025-41450) to its Known Exploited Vulnerabilities catalog on 25 November. Patches for them exist in versions 3.3 and 4.2, and neither outlet links them to the European attacks.
The short version
- CISA warned on 25 November about CVE-2026-129713, a 9.8-severity stack-based buffer overflow in Danfoss AK-SM 8xxA Series controllers, BleepingComputer reported.
- An unauthenticated attacker can crash the server and potentially run code with the web server's privileges, according to CISA.
- Danfoss said on 20 November that a fix will arrive in software version 5.5.x. No patch is available now.
- Also on 25 November, CISA added three older Danfoss AK-SM 800A flaws to its Known Exploited Vulnerabilities catalog, The Hacker News and Security Affairs reported. Danfoss has fixed them in versions 3.3 and 4.2.
- Danfoss controllers were involved in attacks on supermarkets in France in October and in at least 115 stores across seven countries on 2 November, BleepingComputer reported.
What happened
The US Cybersecurity and Infrastructure Security Agency (CISA) warned on 25 November of a critical, unpatched vulnerability in Danfoss AK-SM 8xxA Series controllers, BleepingComputer reported. Food retailers use these devices to manage commercial refrigeration, HVAC and lighting.
Tracked as CVE-2026-129713, the flaw scores 9.8 on the 10-point CVSS severity scale. It is a stack-based buffer overflow in the controller's server. CISA says an attacker can trigger it without logging in, force the server to restart, and potentially achieve remote code execution (running their own commands on the device) with the web server's privileges. Danfoss published an advisory on 20 November saying the fix will come in software version 5.5.x, which will also remove the option to turn off 'Strict mode'. As of BleepingComputer's report, no patch exists.
The product line is called the AK-SM 800A Series and includes the 820A, 850A and 880A models. They act as central control units: they manage refrigerated display cases and compressor racks, log temperatures and raise alerts when readings change. CISA says the controllers are deployed worldwide but that the exact number is unclear.
BleepingComputer linked the warning to recent attacks. Between 11 and 12 October, several French supermarkets and food retailers suffered significant losses after attacks attributed to Iran's IRGC-linked Shahid Kaveh unit, the outlet reported. Those attacks compromised Danfoss AK-SM/AK-SC and Copeland/Dixell XWEB controllers and remotely altered defrost settings.
On 2 November, at least 115 supermarket stores in Belgium, the Netherlands, Sweden, Luxembourg, Ireland, Romania and Estonia had refrigeration shut down or settings changed remotely, BleepingComputer reported. The supplier Sabcobel said the attackers used the same vulnerability as in France. The same day, a refrigeration supplier to the French national blood service had cold-storage settings altered at three facilities, in an incident suspected to be part of the same campaign.
CISA also took a separate action on Wednesday 25 November. The Hacker News and Security Affairs reported that CISA added three earlier Danfoss AK-SM 800A flaws to its Known Exploited Vulnerabilities (KEV) catalog, a list of bugs CISA tracks as exploited in real attacks. They are CVE-2023-25914, a path traversal flaw rated 7.5, CVE-2023-25915, an improper input validation flaw rated 9.8, and CVE-2025-41450, an improper authentication flaw rated 8.2. Security Affairs said there is no public confirmation that attackers used these particular flaws in the European incidents, and neither outlet names an actor behind any exploitation. These three are separate from CVE-2026-129713 and, unlike it, have fixes.
Why it happened
CISA and Danfoss describe the technical fault in CVE-2026-129713 as a stack-based buffer overflow in the controller's server, reachable without authentication. The reports do not say which network service or request triggers it.
It is not stated whether CVE-2026-129713 is the flaw used in the October and November attacks. Sabcobel said the attackers used the same vulnerability as in October, but BleepingComputer's report does not name that vulnerability or confirm it is this CVE. How the earlier attackers reached the controllers has not been detailed either.
Security Affairs described the three KEV-listed flaws this way. CVE-2023-25914 lets an authenticated remote attacker read files from the underlying system through the XML interface, in versions before 3.3. CVE-2023-25915 lets an authenticated remote attacker run arbitrary commands because of weak input checking, also before 3.3. CVE-2025-41450 lets an attacker generate web reports without authorisation, potentially exposing internal IP addresses, usernames and store names, in versions before 4.2. Security Affairs credited the last to researchers at Claroty's Team82. Whether anyone chained these flaws together has not been reported.
How this kind of failure works
Buffer overflows happen when a program copies more data into a fixed-size block of memory than the block can hold. The extra data spills into neighbouring memory. On the stack, the area where a program keeps its working notes about what to do next, that spillover can overwrite the return address, the note telling the program where to resume.
Picture a hotel reception desk with a guest book that has room for 20 characters per name. If the clerk copies a 200-character name into it without checking, the ink runs onto the next page, which holds the instructions for the next task. A careful attacker writes those instructions on purpose. A careless one just crashes the process, which matches CISA's note that the server can be made to restart.
Embedded controllers like these are especially exposed because they often run for years, rarely get updated, and sit on networks reachable from outside for remote monitoring. When the flaw needs no login, anyone who can reach the device can try it. Reducing who can reach it is therefore the first defence while a patch is awaited.
The KEV additions show the other side of the same problem. Flaws fixed in 2023 and 2025 still matter if units in the field never received the update. The planned removal of the option to disable 'Strict mode' suggests Danfoss sees that setting as a protective one, but neither BleepingComputer nor the quoted advisory details what it does, so readers should check Danfoss's advisory rather than assume.
Who is affected
Anyone running Danfoss AK-SM 8xxA Series controllers, including the 820A, 850A and 880A, is in scope. That mainly means supermarket and convenience-store operators, and the contractors who maintain their refrigeration. CISA says the devices are used worldwide.
Version matters. Units running software before 3.3 are listed as affected by CVE-2023-25914 and CVE-2023-25915, and units before 4.2 by CVE-2025-41450, according to Security Affairs. Anyone on those versions has a fix available and should apply it. CVE-2026-129713 has no fix yet.
The practical check is whether a controller's web interface or remote-access service can be reached from the internet, directly or through a poorly secured route. An exposed unit is the greatest worry. A unit behind a firewall and VPN is harder to reach, though not beyond risk if an attacker is already inside the network.
Physical stock is at stake. In the incidents BleepingComputer described, attackers shut down cooling or changed temperature and defrost settings, which spoils food. In the blood-service case, altered cold-storage settings affected three facilities. How much stock was lost has not been given in the report.
How to defend against it
Tick each step as you check it. Your progress is saved on this device.
What to learn from this
The concept: Network segmentation for operational technology
Operational technology (OT) is equipment that controls physical processes, such as cooling, valves or lighting. It often cannot be patched quickly, because updates may need vendor releases, downtime or a site visit. Segmentation means placing it on its own network section, with a firewall deciding what may cross.
Take a supermarket chain. Its checkout tills, office laptops and refrigeration controllers can all sit on one flat network, so a compromised laptop can reach every controller. Split them, and allow only a monitoring server to talk to the controllers, and the same laptop breach no longer touches the cooling.
The same idea applies to building management systems, factory equipment, medical devices and water-treatment controls. When a patch does not exist, as here, segmentation and removing internet exposure are the controls that still work.
When a device cannot be patched yet, limit who can reach it, because an unauthenticated flaw can only be exploited by someone who has a path to it.
Quick check
Sign in to earn 10 XP for a right answer
A critical, unauthenticated flaw is announced in a controller and no patch exists yet. Which step most reduces your risk today?
An unauthenticated flaw does not depend on passwords, so the best protection is to stop attackers reaching the device at all. A password change or reboot does not block the vulnerable service.
Timeline
- 11-12 October 2026 Several French supermarkets and food retailers suffer losses after Danfoss and Copeland/Dixell controllers are compromised and defrost settings altered, BleepingComputer reported.
- 2 November 2026 At least 115 stores in seven European countries have refrigeration shut down or altered remotely; a supplier to the French national blood service is also hit at three facilities.
- 20 November 2026 Danfoss publishes an advisory saying CVE-2026-129713 will be fixed in version 5.5.x.
- 25 November 2026 CISA warns of the unpatched flaw, rated 9.8, in the AK-SM 8xxA Series.
- 25 November 2026 CISA adds CVE-2023-25914, CVE-2023-25915 and CVE-2025-41450, all affecting Danfoss AK-SM 800A units, to its Known Exploited Vulnerabilities catalog, The Hacker News and Security Affairs reported.
What is not known yet
- When Danfoss will release version 5.5.x.
- Whether CVE-2026-129713 is the flaw used in the October and November attacks.
- Whether the three KEV-listed Danfoss flaws were used in the European attacks, and in which incidents CISA saw them exploited. Security Affairs said there is no public confirmation.
- How many AK-SM 8xxA controllers are deployed or exposed to the internet.
- What 'Strict mode' does and why Danfoss is removing the option to disable it.
- Whether CVE-2026-129713 has been exploited in the wild, which BleepingComputer's report does not state.
Questions people ask
What is CVE-2026-129713?
It is a stack-based buffer overflow in the server of Danfoss AK-SM 8xxA Series controllers, scored 9.8 for severity. CISA says an attacker can trigger it without authentication, crash the server and potentially run code with the web server's privileges.
Is there a patch for the Danfoss AK-SM 8xxA flaw?
Not for CVE-2026-129713, according to BleepingComputer's report. Danfoss said on 20 November that the fix will come in the upcoming software version 5.5.x. Until then, CISA advises keeping controllers off the public internet, segregating them behind firewalls and using up-to-date VPNs for remote access.
Which Danfoss flaws has CISA added to its exploited-vulnerabilities catalog?
The Hacker News and Security Affairs reported that CISA added CVE-2023-25914, CVE-2023-25915 and CVE-2025-41450 on 25 November. Danfoss fixed the first two in version 3.3 and the third in version 4.2. CVE-2026-129713 was not in the list the outlets published.
Which Danfoss products are affected?
The advisory covers the AK-SM 8xxA Series, which Danfoss calls the AK-SM 800A Series. It includes the 820A, 850A and 880A models. Depending on the model, they manage refrigeration, HVAC and lighting.
Was this flaw used in the supermarket attacks in Europe?
That is not confirmed. BleepingComputer reported that Danfoss controllers were compromised in attacks in France in October and across seven countries on 2 November. Sabcobel said the same vulnerability was used both times, but the report does not say it is CVE-2026-129713, and Security Affairs said none of the three KEV-listed flaws is publicly confirmed as used in those incidents.
Sources
- BleepingComputer: CISA warns of critical unpatched flaw in Danfoss refrigeration controllers
- The Hacker News: Hackers Exploit 10 Vulnerabilities Across Mitel, Juniper, Vates, and Danfoss Products
- Security Affairs: U.S. CISA adds HPE, Danfoss, Mitel MiCollab, and Vates Xen Orchestra flaws to its Known Exploited Vulnerabilities catalog